Solenoid valve is an on-off control component; cuts off or opens refrigerant flow according to electric signal from controller. Liquid line solenoid valve: before expansion valve; closes automatically when thermostat reaches set temperature, stops liquid supply. Without liquid solenoid valve, refrigerant will continue migrating to evaporator during compressor off period, causing flood-back at next startup. Hot gas defrost solenoid valve: controls high pressure hot gas entering air cooler coil for defrost cycle. Solenoid coil has different voltage options: 24VAC, 220VAC, 380VAC, must match local export power standard. Xiteliduo rack system uses pilot operated solenoid valve for large flow, direct acting type for small capacity circuit. Direct acting: small flow, low pressure difference; pilot operated: big flow, suitable for large refrigeration circuit. Solenoid valve must be installed with flow arrow direction; debris stuck on valve seat causes internal leakage. Valve seat leakage symptom: compressor still pumps down slowly after shutdown, continuous frost on valve outlet side. Refrigeration maintenance & repair judge solenoid leakage when cooling keeps running after room temperature reaches target.